Gas detector MGS 410

Bacharach's MGS-400 Gas Detectors series make compliance with refrigeration safety codes simple and easy, saving time and money on equipment and installation. Using the MGS-400 App (compatible with Android and iOS), users can intuitively use, commision and maintain thei gas detection system without the need for specialty training or tools. Pre-calibrated sensor modules simplify maintenance, take minutes to exchange, and do not require the use of calibration gas.

  • Mobile App interface for easy commissioning and maintenance without specialty tools
  • Plug-and-play pre-calibrated sensor modules for quick, simple sensor replacement
  • Temperature-compensated measurements mitigate false alarms and optimize accuracy in refrigeration applications.
  • Digital and analog communications for integration with BMS/BAS control system
  • Onboard A/V alarms for ASHRAE 15 and EN 378 compliance with no additional hardware


  • MGS-410 Gas Detectors allow installers to daisy-chain power (24V DC) and Modbus communication via RS 485 cables across the system, and can be easily integrated into a BMS / BAS, or with Bacharach's optional MGS-408 Gas Detection Controller.
General
Approvals CE, UL / CSA / IEC EN 61010-1
Weight 480gr
Dimensions Maximum 210x225x85
Gases detected and detection ranges
Refrigerants 1000 ppm
CO2 5000 / 10000 / 20000 / 30000 / 40000 / 50000 ppm
NH3 100 / 1000 / 5000 / 100% LEL
O2 30 Vol%
CO 500 / 1000 ppm
Combustible gases (R-289, R-600, CH4, R-600a, HC-12a, R-717) 5000 ppm
Combustible gases (R-600, CH4, R-290, NH3) 100% LEL
ΝΟ2 20 ppm
Gases detected Butane, Ethylene, Methane, Propane, CO2, CH4, CO, F407F, HFO1234YF, HFO1234ZE, LPG, NH3, NO2, O2, R-134a, R-22, R-290, R-32, R-404A, R-407A, R-407C, R-407F, R-410A, R-422A, R-422D, R-427A, R-448A, R-449A, R-452A, R-507, R-513A, R-600
Ambient conditions
Semiconductor sensor operating temperature -40 το 50 C
Electrochemical sensor operating temperature NH3 100/1000ppm: -40 to 40 C. NH3 5000ppm: -20 to 40 C. CO 500ppm: -40 to 50 C. NO2 20ppm: -20 to 40 C. O2 σε 30%: -20 to 50 C
Pressure 800 to 1100 mbar
Humidity 5 to 90% RH
Electrical characteristics
Output 1 Digital signal to Modbus RTU via RS 485
Connection Daisy-chained
Power supply 19.5-28.5 VDC or 24 VAC (~20%), 4W