Gas detector MGS 410
- Brand: Bacharach
- Product Code: MGS-410
Bacharach's MGS-400 Gas Detectors series make compliance with refrigeration safety codes simple and easy, saving time and money on equipment and installation. Using the MGS-400 App (compatible with Android and iOS), users can intuitively use, commision and maintain thei gas detection system without the need for specialty training or tools. Pre-calibrated sensor modules simplify maintenance, take minutes to exchange, and do not require the use of calibration gas.
- Mobile App interface for easy commissioning and maintenance without specialty tools
- Plug-and-play pre-calibrated sensor modules for quick, simple sensor replacement
- Temperature-compensated measurements mitigate false alarms and optimize accuracy in refrigeration applications.
- Digital and analog communications for integration with BMS/BAS control system
- Onboard A/V alarms for ASHRAE 15 and EN 378 compliance with no additional hardware
- MGS-410 Gas Detectors allow installers to daisy-chain power (24V DC) and Modbus communication via RS 485 cables across the system, and can be easily integrated into a BMS / BAS, or with Bacharach's optional MGS-408 Gas Detection Controller.
General | |
Approvals | CE, UL / CSA / IEC EN 61010-1 |
Weight | 480gr |
Dimensions | Maximum 210x225x85 |
Gases detected and detection ranges | |
Refrigerants | 1000 ppm |
CO2 | 5000 / 10000 / 20000 / 30000 / 40000 / 50000 ppm |
NH3 | 100 / 1000 / 5000 / 100% LEL |
O2 | 30 Vol% |
CO | 500 / 1000 ppm |
Combustible gases (R-289, R-600, CH4, R-600a, HC-12a, R-717) | 5000 ppm |
Combustible gases (R-600, CH4, R-290, NH3) | 100% LEL |
ΝΟ2 | 20 ppm |
Gases detected | Butane, Ethylene, Methane, Propane, CO2, CH4, CO, F407F, HFO1234YF, HFO1234ZE, LPG, NH3, NO2, O2, R-134a, R-22, R-290, R-32, R-404A, R-407A, R-407C, R-407F, R-410A, R-422A, R-422D, R-427A, R-448A, R-449A, R-452A, R-507, R-513A, R-600 |
Ambient conditions | |
Semiconductor sensor operating temperature | -40 το 50 C |
Electrochemical sensor operating temperature | NH3 100/1000ppm: -40 to 40 C. NH3 5000ppm: -20 to 40 C. CO 500ppm: -40 to 50 C. NO2 20ppm: -20 to 40 C. O2 σε 30%: -20 to 50 C |
Pressure | 800 to 1100 mbar |
Humidity | 5 to 90% RH |
Electrical characteristics | |
Output 1 | Digital signal to Modbus RTU via RS 485 |
Connection | Daisy-chained |
Power supply | 19.5-28.5 VDC or 24 VAC (~20%), 4W |